2013 TPI Corporation Electrical Heat Products Catalog - page 35

35
Optional controls must be factory installed. Field installation is not
acceptable and violates Listing and factory warranty.
Wall mounted control panels may control multiple units but cannot
be used if in-built controls are selected.
480V units include 24V transformer and relay as standard (A1) -
only TS option control section can be added. Depth dimension of all
480V models is 10-7/8”
Degree F air rise is measured at 710 F.P.M. and 425 CFM. Throw
designed for 8 to 12 foot ceilings. db RE 10
-12
Watt=63.9
Unit Weight:
50 lbs.
Recommended Remote Thermostats:
Line Voltage:
Single Phase 208-240V
ET5DS
Single Phase 277V
ET5SS
Three Phase
TW1512
Low Voltage:
UT1001
•
White powder coated 20 gauge grill.
•
208V, 240V, & 277V units have manual reset thermal limit.
•
480V units have manual reset thermal limit, 24V control transformer,
and 24V relay (A1 suffix).
• Enclosed steel fin sheath element.
•
Rough in dimensions: 23-1/16” sq. x 9-1/8” deep.
Notes
Standard Models
Product Dimensions
Product Specifications
Features
Factory Installed Control Sections
Contractor shall supply and install heavy duty ceiling mounted
forced air electric heater(s) of the wattage, voltage and phase as
indicated on the plans. The heater shall be so designed to provide an
even distribution of heated air to the space to be heated by drawing
return air in the periphery of the heater, across and through the
element and be discharged from the center section of the heater by
means of an electric motor and axial flow fan blade.
Heaters shall be recessed type and mounted flush with the finished
ceiling. The return grille assembly shall be constructed of a one
piece heavy gauge steel with 1/4” slots for return air and concentric
rings for uniform air discharge. Grille assembly shall be attached to
chassis by tamper-resistant (allen head) machine screws. All parts
of enclosure shall be heavy gauge steel, zinc coated both sides and
finished in neutral off white powder coat paint.
Enclosure shall be constructed of 1/6” x 3/8” rounded edge
horizontal steel louvers which shall be spaced for maximum opening
of 5/16”. Louvers shall be welded at every intersection to evenly
spaced 1/8” diameter vertical members. Discharge grille to have
concentric rings for uniform air discharge. Grille assembly shall be
attached to chassis by tamper-resistant (allen head) machine screws.
All part of enclosure shall be heavy gauge steel, Zinc coated both
sides and finished in neutral off white colored powder coat finish.
Motor shall be permanent lubricated, unit bearing, totally
enclosed, impedance protection. Motors shall operate at no more
than 1300 RPM and shall be same voltage as the heater.
Heaters shall have a rating of 425 CFM at 710 F.P.M. with a
maximum temperature rise of 44°F and 63.9 DB RE 10 12 Watt.
Element assemblies shall consist of two or three corrosion
resistant steel sheathed type elements mechanically bonded to
common corrosion resistant steel fins. Each sheathed element shall
consist of helically coiled Nickel Chromium alloy resistant wire
completely embedded in and surrounded by magnesium oxide,
enclosed and wedged into corrosion resistant steel sheaths. Elements
shall have 2” cold conductor pins extending into sheath and shall
have a density of no more than 60 Watts per inch.
Heaters shall be equipped with a “manual reset” thermal overload
which disconnects elements and motor in the event normal operating
temperatures are exceeded. For safety, if opened due to abnormal
temperature, thermal overload shall remain open until manually
reset. Automatic reset thermal overloads which allow the element
to continue to cycle under abnormal conditions will not be accepted.
Heaters shall be ETL listed.
Manufactured in U.S.A.
*Optional Louver Outlet - $70 Adder
*
SUFFIX
DESCRIPTION
LIST
A1
Transformer with 24V Secondary and 24V Relay
127
S
Disconnect Switch
158
TA1S
Thermostat / Transformer / Disconnect Switch
371
TA1 Single Pole Thermostat and Transformer with 24V Secondary and 24V
Relay
231
A1S Transformer with 24V Secondary and 24V Relay and Disconnect Switch 287
T2
Double Pole Thermostat
126
T2S
Double Pole Thermostat and Disconnect Switch
281
R Relay Control Voltage Same as Heater (control voltage field supplied)
78
R1
Relay 24V Control Voltage (control voltage field supplied)
127
R2
Relay 120V Control Voltage (control voltage field supplied)
117
T
Single Pole (480V only)
95
L
Factory installed adjustable louver diffuser option.
91
3480 Series Commercial Fan Forced Recessed Mounted Ceiling Heater
UPC#
686344 MODEL KW BTU’S VOLTS PH AMPS TEMP
RISE LIST
367653
F3482
2 6826
208
1
9.6
15 °F 1334
367677
H3482
240
8.3
367660
G3482
277
7.2
318471 P3482A1
480
4.2
1460
470186
J3482
2 6826
208
3
5.6
15 °F 1431
470209
K3482
240
4.8
470247 Y3482A1
480
2.4
1557
367684
F3483
3
10200
208
1
14.4
22 °F
1350
367707
H3483
240
12.5
367691
G3483
277
10.8
318488 P3483A1
480
6.3
1476
470193
J3483
3
208
3
8.3
1448
470216
K3483
240
7.2
470254 Y3483A1
480
3.6
1573
367714
F3484
4
13600
208
1
19.2
30 °F
1366
367738
H3484
240
16.8
367721
G3484
277
14.4
318501 P3484A1
480
8.3
1490
367745
J3484
4
208
3
11.1
1475
367752
K3484
240
9.7
318587 Y3484A1
480
4.8
1601
367769
F3485
5
17000
208
1
24.1
37 °F
1532
367783
H3485
240
20.8
367776
G3485
277
18.1
318549 P3485A1
480
10.4
1665
367790
J3485
5
208
3
13.9
1626
367806
K3485
240
12.1
318402 Y3485A1
480
6.1
1755
366106
PT3480
Recess Frame - Weight 5 lbs.
142
International Models
470971 M3482T2i
2 6826 220
1
9.1 15 °F 1334
470988 N3482T2i
240
8.3
470995 M3483T2i
3 10200 220
13.6 22 °F 1350
471008 N3483T2i
240
12.5
471015 M3484T2i
4 13600 220
18.2 30 °F 1366
471022 N3484T2i
240
16.7
1...,25,26,27,28,29,30,31,32,33,34 36,37,38,39,40,41,42,43,44,45,...111